Hochiki CZM CONVENTIONAL ZONE INPUT MODULE (DCP-CZM)

Hochiki CZM CONVENTIONAL ZONE INPUT MODULE (DCP-CZM)

Por encomenda

Descrição

UL 864 9th Edition Listed Provides an addressable point for a zone of up to 25 conventional smoke detectors Blinks green when being polled by the fire panel Latches on red when activated (controlled by panel) Device address can b…

  • EstadoNovo
  • Garantia1 ano
  • MarcaHochiki
  • ReferênciaDCP-CZM
  • CódigoSL-08493
  • EntregaLuanda, combinada no pedido
  • ModeloDCP-CZM
  • GamaI/O Modules
  • CorIvory
Ver mais informaçõesVer menos

UL 864 9th Edition Listed Provides an addressable point for a zone of up to 25 conventional smoke detectors Blinks green when being polled by the fire panel Latches on red when activated (controlled by panel) Device address can be programmed with a handheld programmer. Device address- ranges from 1 to 127 Compatible with Class A and Class B wiring Auxiliary power source required to provide power for the zone of detectors Compatible with conventional smoke detectors, SOE-24V, SOE-24H, SOC-24V,SOC-24VN, SLV, SLR, SLK, SIH, SIJ, and conventional heat detectors, DCD, DFE, and DSC

• The Conventional Zone Module (DCP-CZM) is designed for use on an analog addressable Fire Alarm system. Up to 127 devices can be placed on a single SLC loop. The device address is uniquely stored on an onboard EEPROM. The module allows the panel to interface and monitor two-wire conventional detectors or pull stations. Each DCP-CZM transmits the status on one zone of devices (25 maximum per zone) back to the panel. It supervises the power supply as well as the entire zone of devices.